Festo AG & Co. KG

8126915
operator unit
CDSA-D3-RV

More detailed information about this product!

Festo Data sheet

CriterionFeature
Number of function keys20
Number of system LEDs5
DisplayLCD-Display
With background illumination
Display propertyTouchscreen
Display size7"
Control elementsMembrane keypad
Enable control unit
Emergency stop button
Input current<= 5,6 A
Operating voltage range DC19,2 - 30 V
Display resolutionWSVGA, 600x1024 pixels
AuthorisationCCC
RCM Mark
c UL us - Listed (OL)
KC markKC-EMV
CE mark (see declaration of conformity)to EU directive for EMC
to EU directive for machinery
in accordance with EU RoHS directive
UKCA marking (see declaration of conformity)To UK instructions for EMC
To UK instructions for machines
To UK RoHS instructions
Certificate issuing departmentUL E239998
Storage temperature-20 - 70 °C
Relative air humidity5 - 95 %
Protection classIP65
Note on degree of protectionWhen USB cover flap is closed
in assembled condition
Safety classIII
Ambient temperature0 - 40 °C
Product weight950 g
Electrical power consumption12 W
IP address allocationFCT
DHCP
Nominal operating voltage DC24 V
Power failure buffering10 ms
Nominal altitude of use<= 2000 m NHN
Power supply, functionEnable control
Emergency stop
Power supply
Power supply, type of connectionSocket strip
Power supply, connection technologySocket strip 12 pins, 2 rows
Power supply, number of pins/wires12
Power supply, assigned pins/wires6
USB interface, connection technologyUSB 2.0 Typ A
USB interface, connection pattern00995868
Ethernet interface, protocolTCP/IP
Ethernet interface, functiondiagnosis
Network connection to PLC
Parameterisation
Ethernet interface, type of connectionPlug socket
Ethernet interface, connection technologyRJ45
Ethernet interface, number of pins/wires8
Ethernet interface, transmission rate100 Mbit/s
Materials noteContains PWIS substances
Conforms to RoHS
Material housingABS
Dimensions W x L x H212 mm x 251 mm x 73 mm
Note on acceptable current load at 40°C10 - 1000 mA at each emergency stop contact
< 500 mA for enable control unit
Utilisation categoryDC-13, emergency stop
Service life characteristic value B10d, subcomponent0.25 million switching cycles, emergency stop
1 million switching cycles, enable control unit

© 2022 Festo AG & Co. KG