Festo AG & Co. KG
4080497
bus module
CPX-E-PN
More detailed information about this product!
Festo Data sheet
Criterion | Feature |
Dimensions W x L x H | 42,2 mm x 125,8 mm x 76,5 mm |
Grid dimension | 18,9 mm |
Diagnostics via LED | Force mode Network errors Network status port 1 Network status port 2 Power supply electronics/sensors Power supply load System error Maintenance required |
Diagnostics via bus | Wire break Short circuit PROFIsafe addresses different parameterisation error Upper limit value not observed Overtemperature Lower limit value not observed Undervoltage |
Configuration support | GSDML file |
Max. no. of modules | 10 |
Additional functions | LLDP MRP MRPD PROFINET FSU PROFINET I&MO..3, 1..3 retentive memory possible PROFINET Shared device S2 system redundancy SNMP |
System parameters | Diagnostic memory Fail-safe reaction Force mode System start |
Module parameters | Channel alarms bundling Undervoltage diagnostics Channel alarms undervoltage Process value representation of analogue modules |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 75 mA |
Max. power supply | 8 A |
Nominal operating voltage DC for electronics/sensors | 24 V |
Power failure buffering | 20 ms |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Power supply, function | Electronics and sensors |
Power supply, type of connection | Terminal strip |
Power supply, connection technology | Cage clamp terminal |
Power supply, number of pins/wires | 4 |
Power supply, conductor diameter | 0,2 - 1,5 mm2 |
Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Authorisation | RCM Mark c UL us - Listed (OL) |
KC mark | KC-EMV |
CE mark (see declaration of conformity) | to EU directive for EMC |
Certificate issuing department | UL E239998 |
Vibration resistance | Transport application test at severity level 1 in accordance with FN 942017-4 and EN 60068-2-6 |
Shock resistance | Shock test with severity level 1 in accordance with FN 942017-5 and EN 60068-2-27 |
Corrosion resistance classification CRC | 0 - No corrosion stress |
Storage temperature | -20 - 70 °C |
Relative air humidity | 95 % non-condensing |
Protection against direct and indirect contact | Protective extra-low voltage with safe disconnection (PELV) |
Protection class | IP20 |
Ambient temperature | -5 - 50 °C |
Note on ambient temperature | -5 - 60°C for vertical installation |
Product weight | 145 g |
Maximum address volume for outputs | 64 Byte |
Note on outputs | 62 bytes with I/O diagnostic interface 64 bytes with status bits 64 bytes without diagnostics |
Maximum address volume for inputs | 64 Byte |
Note on inlets | 62 bytes with I/O diagnostic interface 62 bytes with status bits 64 bytes without diagnostics |
Fieldbus interface, electrical isolation | Yes |
Fieldbus interface, transmission rate | 100 Mbit/s |
Fieldbus interface | Ethernet |
Fieldbus interface, type of connection | 2x socket |
Fieldbus interface, connection technology | RJ45 |
Fieldbus interface, number of pins/wires | 8 |
Fieldbus interface, protocol | PROFINET IRT PROFINET RT |
Fieldbus interface, max. address volume for inputs | 64 Byte |
Fieldbus interface, max. address volume for outputs | 64 Byte |
Mounting type | with top-hat rail |
Materials note | Contains PWIS substances Conforms to RoHS |
Material housing | PA |
© 2022 Festo AG & Co. KG