Criterion | Feature |
Dimensions W x L x H | 18,9 mm x 76,6 mm x 124,3 mm |
Grid dimension | 18,9 mm |
No. of inputs | 4 |
Diagnostics via LED | Error per channel Error per module |
Diagnostics via bus | Wire break Short circuit/overload in sensor supply Parameter error parameterisation error Overload at analogue inputs Upper limit value not observed Overflow/underflow Lower limit value not observed |
Measured variable | Voltage Current |
Module parameters | Parameterisation error diagnostics Short circuit diagnostics for sensor supply Behaviour after short circuit/overload Data format analogue inputs Deactivate sensor supply Diagnostics of overload at analogue inputs Behaviour after overload at analogue inputs Hysteresis limit monitoring |
Channel parameters | Signal range per channel Diagnostics for lower limit Diagnostics for upper limit Wire break diagnostics Underflow/overflow diagnostics Parameter error diagnostics Smoothing factor Lower/upper limits |
Repetition accuracy | ±0.1% at 25 °C |
Protection (short circuit) | Internal electronic fuse protection per module |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | typ. 70 mA |
Operating error limit related to the ambient temperature range | ±0,3 % |
Basic error limit at 25°C | ±0,2 % |
Max. residual current inputs per module | 1,4 A |
Nominal operating voltage DC for electronics/sensors | 24 V |
Power failure buffering | 10 ms |
Electrical isolation channel – internal bus | Yes |
Electrical isolation channel – channel | No |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Authorisation | RCM Mark c UL us - Listed (OL) |
KC mark | KC-EMV |
CE mark (see declaration of conformity) | to EU directive for EMC |
Certificate issuing department | UL E239998 |
Vibration resistance | Transport application test at severity level 1 in accordance with FN 942017-4 and EN 60068-2-6 |
Shock resistance | Shock test with severity level 1 in accordance with FN 942017-5 and EN 60068-2-27 |
Corrosion resistance classification CRC | 0 - No corrosion stress |
Storage temperature | -20 - 70 °C |
Relative air humidity | 95 % non-condensing |
Protection class | IP20 |
Ambient temperature | -5 - 50 °C |
Note on ambient temperature | -5 - 60°C for vertical installation |
Product weight | 96 g |
Maximum address volume for inputs | 8 Byte |
Signal range | -10 - 10 V -20 - 20 mA -5 - 5 V 0 - 10 V 0 - 20 mA 1 - 5 V 4 - 20 mA |
Data format | 15 bits + prefix Linear scaling |
Max. line length | 30 m Shielded |
Electrical connection, input, function | Analogue input |
Electrical connection, input, connection type | 4x terminal strips |
Electrical connection, input, connection technology | Cage clamp terminal |
Electrical connection, input, number of pins/wires | 4 |
Electrical connection for input, conductor cross section | 0,2 - 1,5 mm2 |
Electrical connection for input, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Electrical connection for input 2, function | Functional earth |
Electrical connection for input 2, connection type | Terminal strip |
Electrical connection for input 2, connection technology | Cage clamp terminal |
Electrical connection for input 2, number of pins/wires | 4 |
Electrical connection for input 2, connection pattern | 00995842 |
Electrical connection for input 2, conductor cross section | 0,2 - 1,5 mm2 |
Electrical connection for input 2, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Mounting type | with top-hat rail |
Materials note | Contains PWIS substances Conforms to RoHS |